ARI-1500
This is a 15 horsepower, air-cooled
chiller with space heating option. This unit is used for cooling
insulating oil used in the manufacture and testing of Transformers. Its
duty is to cool 15,000 gallons of oil from 203 degrees F to 77 degrees F
in 27 hours or less. The heat which is removed from the oil during this
cool down process is used for space heating of the plant in the winter.
Plant air is drawn into the mixing box through the return air dampers
(right side of top photo below). The air passes through the condenser
coil and is heated to approximately 100 degrees F. The air is then
discharged out of the top of the unit by two centrifugal blowers (not
visible). This air is then distributed through the shop by a duct
system provided by the customer. In the summer the condenser air is
drawn from outside and returned there by the duct system. Dampers in
the supply ducts are used to divert air inside or outside. The quantity
of heat available for space heating is 300,000 BTU/H.
Back to Products
|